Kim Lighting KFL1-16L-40-3K8-HF-UNV-Y-BLS Small Architectural LED Floodlight, Yoke Mount, 120-277V, 40W, 4000 Lumens, 80 CRI, Horizontal Flood Beam, 3000K, Black Gloss Smooth

Kim Lighting

$1,508.00
(No reviews yet) Write a Review
Color:
Black Gloss Smooth
Color Temperature:
3000K
Wattage:
40W
Lumens:
4000
Beam:
Horizontal Flood
Adding to cart… The item has been added
PICTURE MAY NOT REPRESENT ACTUAL ITEM FINISH. PLEASE REFER TO PRODUCT DESCRIPTION.

Construction
• One piece die-cast, low copper (<0.6% Cu) Aluminum Alloy 360 with vents and .100" minimum wall thickness
• Finish: fade and abrasion resistant, electrostatically applied, thermally cured, triglycidal isocyanurate (TGIC) polyester powdercoat
• Lens is impact resistant 1/8" tempered glass with anti-reflective coating
• Lens has a one-piece extruded vulcanized silicone gasket
• Lens frame one piece die-cast, low copper (<0.6% Cu) Aluminum Alloy 360 and .100" minimum wall thickness
• Lens frame has a one-piece O-ring extruded vulcanized silicone gasket
• Mid-frame one piece die-cast, low copper (<0.6% Cu) Aluminum Alloy 360 and .100" minimum wall thickness
• Mid-frame secures to lens frame and housing by stainless steel recessed Allen-head screws
• Silicone gaskets throughout
• All external fasteners are stainless steel

Optics
• LEDs mount to a metal printed circuit board assembly (MCPCB)
• Optical lenses are clear injection molded PMMA acrylic

Installation
• Fixtures must be grounded in accordance with national, state and/or local electrical codes

Electrical
• Universal voltage, 120 through 277V with a +/- 10% tolerance
• Driver is Underwriters Laboratories recognized
• Drivers shall have greater than a 0.9 power factor, less than 20% harmonic distortion, and be suitable for operation in -40°C to 40°C ambient environments
• Luminaire shall be capable of operating at 100% brightness in a 40°C environment
• Both driver and optical array have integral thermal protection that will dim the luminaire upon detection of temperatures in excess of 85°C
• Dimming range from 10% to 100% through the use of standard 0-10V interface on the programmable driver
• Modular wiring harness in the service area provides user access to the dimming circuitry

For more information, Click Here - PDF